1.1

95-8572



Figure 3 shows the terminal configuration for the R8471J
Controller.

Terminals 1 and 2 – 4 to 20 mA dc output.

non-Isolated current output -

If the 4 to 20 mA current loop
is to be non-isolated, wire the
system as shown in Figure 4.
Note that terminal 2 is not used
with a non-isolated current loop.
Program the unit for a non-isolated
current loop as described in the
“Controller Programming” section
of this manual.

Isolated current output - If an

isolated current loop is desired,
wire the system as shown in
Figure 5 and program the unit
for an isolated current loop as
described in the “Controller
Programming” section of this
manual. Note that this wiring
scheme requires an external
power source for the isolated
current output.

cUrrent oUtPUt

cHaSSIS GroUnD

PoWer

SenSor

external reSet

HIGH alarM

HIGH alarM / oc

aUx. alarM

aUx. alarM / oc

loW alarM

loW alarM / oc

FaUlt

FaUlt / oc

1

3

4

5

6

7

8

9

10

11

12

13

14

15

16

+

+

+

18 to 32

vDc

PoWer

SIGnal

2

oc = oPen collector oUtPUt

(BaSe MoDel onlY)

B190

Figure 3—Terminal Configuration for R8471J Controller

ISOLATED OUTPUT
CURRENT LOOP

CHASSIS GROUND

POWER

SENSOR

EXTERNAL RESET

HIGH ALARM

HIGH ALARM / OC

AUX. ALARM

AUX. ALARM / OC

LOW ALARM

LOW ALARM / OC

FAULT

FAULT / OC

1

3

4

5

6

7

8

9

10

11

12

13

14

15

16

+

+

+

18 TO 32VDC

GROUND

POWER

SIGNAL

HIGH

ALARM

AUXILIARY

ALARM

LOW

ALARM

FAULT

RESET

24

VDC

+

2

4-20 MA

A2412

R8471J CONTROLLER

*

*

*

NO CONNECTION

OC = OPEN COLLECTOR OUTPUT

(BASE MODEL ONLY)

–24 VDC

+24 VDC

– 4-20 MA

1

2

3

4

5

6

7

8

9

10

11

12

13

MODEL OPECL

GAS DETECTOR

+ 4-20 MA

–24 VDC

+24 VDC

2

1

NOTES: 1 INTERNAL JUMPER REQUIRED

FOR NON-ISOLATED CURRENT

OUTPUT (SINGLE POWER

SUPPLY).

2 250 OHM RESISTOR REQUIRED.

Figure 4—A Typical System with Relay Outputs and Non-Isolated Current Output