1.1

7. Attach the sensor to the junction box. Do

not

over

tighten.

NOTE

Coat the sensor threads with an appropriate
grease to ease installation. Also lubricate the
junction box cover threads. The recommended
lubricant is a silicone free polyalphaolefin grease,
available from Detector Electronics. If catalytic
combustible sensors are present,
do not use a
silicone based grease.

8. Connect the sensor wires to the sensor terminal

block inside the junction box. (See Figure 6.)
Connect the controller wiring to the controller
terminal block inside the junction box.

Connect the shield to earth ground at the controller
end only. Under normal conditions, the other end
of the shield should not be connected at the sensor
junction box.

The wiring code is:

Red

lead =

“+/power”

Black

lead

=

“-/signal”

Green lead = Chassis (earth) ground

In order to maintain the intrinsically safe rating of the
C7067E chlorine sensor, it must be wired through an
approved I.S. barrier. See Figure 7.

NOTE

When an I.S. barrier is used, the input voltage
(measured at the controller) must be between 23
and 26.6 vdc to ensure proper operation of the
sensor and barrier.

9. Check the sensor wiring to ensure proper

connections, then pour the conduit seals and allow
them to dry (if conduit is being used).

10. Place the cover back on the junction box.

SENSOR

GROUND

BLK (–) TO TERMINAL 7

RED (+) TO TERMINAL 6

WIRING TO CONTROLLER

GROUND JUNCTION BOX
ACCORDING TO LOCAL CODES

B1528

RED

BLK

GRN

=
=
=

+

GROUND

FIBER FILLER

SEALING COMPOUIND

Figure 6—Sensor Wiring

CURRENT OUTPUT

CHASSIS GROUND

POWER

SENSOR

EXTERNAL RESET

HIGH ALARM

HIGH ALARM / OC

AUX. ALARM

AUX. ALARM / OC

LOW ALARM

LOW ALARM / OC

FAULT

FAULT / OC

1

3

4

5

6

7

8

9

10

11

12

13

14

15

16

+

+

+

18 TO 32

VDC

POWER

SIGNAL

24

VDC

*

+

C7067E

SENSOR

2

A1704

R8471D CONTROLLER

BLK

RED

GREEN

+

MTL 787S

OR

MTL 788

OC = OPEN COLLECTOR OUTPUT

(BASE MODEL ONLY)

*

WHEN USING AN I. S. BARRIER,

INPUT VOLTAGE MUST BE 23 TO 26.6 VDC.

Figure 7—R8471D Controller and C7067E Sensor

Used with I.S. Barrier