Base Controller

Connections to open collector

transistor outputs are made at terminals 10, 12, 14,
and 16. Terminals 9, 11, 13, and 15 are not used.
See Figure 13 for an example of a typical connection
to an open collector transistor output.

NOTE

External equipment that can generate transients
when switching (such as relays) must have
a transient suppression device
(diode)
connected across the coil at the time of
installation. (Note proper polarity of the diode.)
This will safeguard the output transistors of the
controller against possible damage. Figure 13
illustrates an inductive load with a diode used for
transient suppression.

Premium Controller

The relay outputs (terminals

9 to 16) are programmed for the desired operation
using the procedure described in the “Controller
Programming” section of this manual.

100K

OPEN COLLECTOR OUTPUT

1N4004

TYPICAL

+32 VDC MAXIMUM

B1289

Figure 13—Open Collector Output with Inductive Load and

Transient Suppression Device