1.1

12

Terminal 3 –

Connect to chassis (earth)
ground. Ground the cable
shield at this terminal.

Terminal 4 –

Connect to the positive (+) side
of the 24 vdc power source.

Terminal 5 –

Connect to the negative (-)
side of the dc power source.

NOTE

If local wiring codes permit and if a ground fault
monitoring system is not being used, the minus
side of the dc power source can be connected
to chassis (earth) ground. Alternatively, a 0.47
microfarad, 100 volt capacitor can be installed
(terminal 5 to ground) for best immunity against
electromagnetic interference.

Terminal 6 –

Connect to the red (+) lead of
the sensor.

Terminal 7 –

Connect to the black (-) lead of
the sensor.

Terminal 8 –

A normally open momentary
c l o s u r e s w i t c h c a n b e
c o n n e c t e d b e t w e e n t h i s
terminal and the negative (-)
side of the power source for
remote reset.

Terminals 9 and 10 – High Alarm Output.

Terminals 11 and 12 – Auxiliary Alarm Output.

Terminals 13 and 14 – Low Alarm Output.

Terminals 15 and 16 – Fault Output.

CURRENT OUTPUT

CHASSIS GROUND

POWER

SENSOR

EXTERNAL RESET

HIGH ALARM

HIGH ALARM / OC

AUX. ALARM

AUX. ALARM / OC

LOW ALARM

LOW ALARM / OC

FAULT

FAULT / OC

1

3

4

5

6

7

8

9

10

11

12

13

14

15

16

+

+

+

18 TO 32

VDC

POWER

SIGNAL

HIGH

ALARM

AUXILIARY

ALARM

LOW

ALARM

FAULT

RESET

24

VDC

+

SENSOR

2

R8471 SERIES CONTROLLER

4 TO 20 MA

BLK

RED

GREEN

+

OC = OPEN COLLECTOR OUTPUT

(BASE MODEL ONLY)

Figure 11—A Typical System - Controller with Relay Outputs and

Non-Isolated Current Output

CURRENT OUTPUT

CHASSIS GROUND

POWER

SENSOR

EXTERNAL RESET

HIGH ALARM

HIGH ALARM / OC

AUX. ALARM

AUX. ALARM / OC

LOW ALARM

LOW ALARM / OC

FAULT

FAULT / OC

1

3

4

5

6

7

8

9

10

11

12

13

14

15

16

+

+

+

18 TO 32

VDC

POWER

SIGNAL

HIGH

ALARM

AUXILIARY

ALARM

LOW

ALARM

FAULT

RESET

24

VDC

+

SENSOR

2

R8471 SERIES CONTROLLER

4 TO 20 MA

BLK

RED

GREEN

+

24

VDC

+

OC = OPEN COLLECTOR OUTPUT

(BASE MODEL ONLY)

Figure 12—A Typical System - Controller with Isolated

Current Output