Det-Tronics R8471NH34001,2,3 Single Channel Gas Controller, NH3 User Manual

Page 16

Advertising
background image

95-8529

1.1

14

CONTROLLER PROGRAMMING

Refer to Figure 14 to determine the location of
programming jumpers and switches. Table 5 shows
the selectable options for each relay.

IMPORTANT

All jumper plugs must be installed. The
controller outputs will not function properly if a
jumper plug is missing.

Normally Open/Closed Relays

The four relays are individually programmed for either
normally open or normally closed contacts. This
is accomplished by placing a jumper plug on the
appropriate pair of pins. Each relay has a set of
three pins. For normally open operation, place the
plug on the NO and center pins. For normally closed
operation, place it on the NC and center pins. The
pin groups are identified as follows:

J2 – High Alarm
J3 – Auxiliary Alarm
J4 – Low Alarm
J5 – Fault

The controller is programmed at the factory for
normally open relay contacts.

A1392

HIGH ALARM (J2)

SW1-1

CLOSED = LATCHING
OPEN = NON-LATCHING

SW1-2

CLOSED = NORMALLY ENERGIZED
OPEN = NORMALLY DE-ENERGIZED

LOW ALARM (J4)

FAULT (J5)

AUXILLIARY ALARM (J3)

NORMALLY

OPEN/CLOSED

RELAY CONTACTS

J1

INT = NON-ISOLATED
EXT = ISOLATED

Figure 14—Programming Jumper Plugs and Switches