Filterwheel Motor

This motor is a small 115 vac shaded pole ball bear-
ing motor. The filterwheel is attached to the motor
shaft.

Filterwheel

The filterwheel is located between the receiver lens
and the photodetector. It contains the DENOMINA-
TOR (active) and NUMERATOR (reference) optical
interference filters. Rotating at a rapid rate, the filter-
wheel chops the incoming light beam and alternately
passes infrared light at the two distinct wavelengths
to the photodetector.

Sync Pickoff

The sync pickoff is a small U-shaped optical switch,
which is mounted on the rear panel printed circuit
board and straddles the filterwheel. It senses when
each filter is in front of the infrared photodetector and
generates the synchronization signal.

Photodetector

The infrared photodetector is mounted at the focal
point of the receiver lens. The photodetector converts
the intensity of the incoming infrared light to a propor-
tional electrical signal. It alternately senses the light
intensity at both wavelengths during each revolution
of the filterwheel. The photodetector is thermo-electri-
cally cooled to increase the sensitivity to infrared light.

Amplifiers

The signal at the photodetector is amplified by the
preamplifier circuitry. The gain of the preamplifier
can be adjusted with a potentiometer to optimize the
signal strength for long or short operating distances.

The amplified signal is fed to the AGC amplifier,
which maintains the signal within the proper operating
range.

Signal Processing Electronics

The signal from the AGC Amplifier is separated into
two outputs: active (DENOMINATOR) and reference
(NUMERATOR).

Ratiometer

The ratiometer circuit generates an analog output by
calculating the ratio of the NUMERATOR (reference)
signal to the DENOMINATOR (active) signal.

Optional 4 To 20 Milliampere Converter

This option converts the 0 to 10 vdc voltage (RATIO
output) into a 4 to 20 ma current. A load resistor is
connected between the RATIO output and the analog
ground and can be any value between 0 and 500
ohms.

3

95-8400

Figure 1—Functional Block Diagram

SIGNAL

PROCESSING

ELECTRONICS

RATIOMETER

OPTIONAL

4 TO 20 MA

CONVERTER

THRESHOLD

DETECTOR

THRESHOLD

DETECTOR

STATUS

ALARM

RELAY

ALARM

RELAY

OPTIONAL

ANALOG

OUTPUT

ANALOG

OUTPUT

AMPLIFIER

MOTOR

INFRARED

PHOTO

DETECTOR

THERMOELECTRIC

COOLER

CONTROL

TRANS-
MITTER

LAMP

VAPOR CLOUD

BEING DETECTED

RECEIVER OPTICS

SYNC PICKOFF

MANUAL
GAIN
CONTROL

DENOM.

NUM.

MODE

SELECT

RATIO

OPTICAL
FILTERS

FILTER
WHEEL

TRANSMITTER

OPTICS

REGULATED

DC

POWER

SUPPLY

ADJUST

A1393

Advertising