Det-Tronics PW9200x Pathwatch IR Gas Detection System User Manual

Page 7

Advertising
background image

5

95-8400

Align

A shorter response time (approximately 2 seconds) is
used only during the alignment and testing process.

Operate

A longer response time (approximately 20 seconds) is
used during normal operation to compensate for short
term signal variations and to prevent the hydrocarbon
alarm from activating on short duration vapor clouds.

Test

Test mode activates the hydrocarbon alarm circuits.

CALIBRATION ADJUSTMENT POTENTIOMETER

The CALIBRATION ADJUSTMENT potentiometer is
used to scale the RATIO output voltage for the
desired span. During factory calibration, the RATIO
output voltage is set to correspond to the desired
ppm reading at full scale.

SENSITIVITY SWITCH

The SENSITIVITY selector permits adjustment of the
range or span of the instrument’s sensitivity. It is rec-
ommended that the selector be set for Hi. Mid and Lo
are used for specialized applications.

ZERO

OUTPUT

OPERATE

ALIGN

TEST

O

V

mA

LO

MID

HI

CALIBRATION
ADJUSTMENT

SET-

POINT

RATIO

DENOM

NUM

MODE

SENSITIVITY

VAPOR ALARM

OUTPUT

SIG GND

OUT OPT

OUTPUT

SELECT

A1395

SPARE

FUSE

1 A

FUSE 1 A

ADJUST

Figure 2—Front Panel Controls