Det-Tronics EagleVision - PC User Manual

Page 70

Advertising
background image

From the Point Configuration screen, highlight the IDC, then click on
Display Point or select Point from the View menu. The IDC Point Display
screen will be displayed. See Figure VII–9.

S

TATUS

I

NDICATORS

Low Voltage. The low voltage bit is set when the input power voltage
to the IDC is below 17.5 volts.

Com 1 and Com 2. One of these bits is set when the IDC’s fault iso-
lation circuitry has detected and isolated a LON wiring fault.

Unable to Configure. This bit is set by the gateway when it was
unable to successfully transfer configuration information to the IDC.

Inhibit Active. This bit indicates that the gateway relays and display
are inhibited from responding to changes in the IDC status. The Inhibit
Active status bit is controlled by the “Inhibit” button.

Not Communicating. This bit is set by the gateway when its diag-
nostic routine indicates that it has not received periodic status messages
from the IDC. The bit is cleared when a new status update is received.

95-8479

7.13

E

AGLE

Q

UANTUM

P

OINT

D

ISPLAYS

IDC P

OINT

D

ISPLAY

FIGURE VII-9

IDC Point Display Screen

Advertising