This screen displays the type and address of each detected board. A
command can be sent to the logic controller to poll for all available
boards by pressing the “Detect Cards” button. This command takes
approximately 20 seconds and the logic controller must be in program
mode. This list can also aid in finding wrong address settings.

L

OCAL

H

ARDWARE

Click on the Local Hardware tab to display the Logic Controller Scan
Time screen. See Figure X–3. The logic controller scan times are used to
measure the logic controller’s performance. The numbers represent the
time required to update the input image table, process up to 32 pages
of custom logic, and update all the output field devices. Typical times
range from 300 to 900 milliseconds, however, the times can increase
depending on the number and type of field devices and the amount of
logic being performed.

10.2

L

OGIC

C

ONTROLLER

D

IAGNOSTICS

FIGURE X-2

LIOU Cards Detected by the
Logic Controller