Installation Step 1: Mount and Wire All System Components

Monitor –

Before mounting the

monitor, ensure that space allows for monitor to be

rotated and calibrated. Disconnect all electrical connections.

Mount the monitor onto base:

o

Flanged Base – Mount the monitor onto an appropriate flat-

face flange with 5/8-11 UNC grade 5, carbon steel or

stainless steel bolts & nuts (3” flange or DN80-PN16: 4 bolts,

4” flange: 8 bolts). Seal flange joint with gasket or suitable

flange sealant, and torque bolts uniformly (20 ft-lbs at a time

in a crisscross pattern) to 60-70 ft-lbs using blue Loctite 242

or equivalent.

o

Threaded Base – Thread monitor onto appropriate threaded

pipe using Loctite 592 or equivalent thread sealant. Tighten

using a strap wrench on the hex portion of the monitor base.

If the monitor will use a CAN line to communicate with other EXM components, connect plug 1

leads to the appropriate CAN line leads.

o

If the monitor will use RF (radio frequency) to communicate with other EXM components,

no preparations are required. The monitor is already RF enabled.

o

If the CAN leads will not be used, replace wires with appropriate plugs.

Supply power to the monitor by connecting the red and black leads from the 6 pin connector to

an appropriate power source. Install a 20 Amp fuse into the positive power lead for a 12V

system (10 Amp for 24V system) to protect the monitor electrical components.

Refer to the respective plug figures for information on the plugs’ pins.

Caution:

Do NOT use motors or discharge as leverage to tighten monitor.

Warning:

When installing the monitor on a raised face companion flange, it is critical

that the bolts be tightened uniformly to prevent misalignment of the monitor relative to
the flange or valve. If the monitor becomes misaligned, the base flange will fracture and
fail when the bolts on the “high” side are tightened.