SYSTEM SPECIFICATIONS
7200 EXM Monitor

Max Flow Rating

1250 GPM (4731 LPM)

Max Operating Pressure

250 PSI Continuous (17.2 BAR)

500 PSI Limited Duty (34.5 BAR)

[50% / 1hr (30min on / 30 min off)]

Inlet Size

3”-150# Flange, DN80-PN16 Flange, 4”-150# Flange,

3” NPT, 3” BSPT

Outlet Size

2.5” Male NHT, 2.5” Male BSPP

Travel

V: -45° to +120°

H: L175° to R175°

Movement

Sealed Electric Motors

Swing Radius

6”

Stow Height

16”

Weight

31 Lbs.

Operating temperature range

-40°F to +185°F (-40°C to +85°C)

Environmental Rating

NEMA 4


Monitor Controller

Input power

12/24 VDC (11-27 VDC)

Control Communication

CAN bus J1939

2.4 Ghz digital radio frequency (unlicensed)

Electrical Load

See Table 1 Below

Fuse Rating

20 AMPS (12V) & 10 AMPS (24V)

RF power output

Meets FCC part 15 requirements for license free operation

Operating temperature range

-40

o

F to +185

o

F (-40

o

C to +85

o

C)

Environmental Rating

NEMA 4

FCC ID

KQL-2510100

7200 SD – Standard Duty Motors

Motor (12 VDC)

Left/Right

Up/Down

Nozzle

Run Current

3 A

3 A

0.5 A

Stall Current

10 A

10 A

NA

Current Trip Point

6.5 A

6.5 A

4 A

7200 HD – Heavy Duty Motors

Motor (12 VDC)

Left/Right

Up/Down

Nozzle

Run Current

5 A

5 A

0.5 A

Stall Current

70 A

70 A

NA

Current Trip Point

20 A

20 A

4 A

Table 1: Motor Current Specifications



Panel Mount Controller - 7010

Input power

12/24 VDC (11 VDC to 27 VDC)

Electrical Load

0.5 AMPS

Fuse Rating

1 AMPS (12V) & 0.5 AMPS (24V)