17

3.

Auxiliary Input 3 – Will open all Foam Valves or Auxiliary Devices for the monitors included in the

specific network. To activate this function wire a normally opened pushbutton between terminal block
75 and 24VDC for the original OCP Revision and to terminal 51 (or 51A) when using the internal
24VDC from the panel on later Revisions.

4.

Auxiliary Input 4 – Will signal all monitors included in the specific network to perform the Park

function. To activate this function wire a normally opened pushbutton between terminal block 76 and
24VDC for the original OCP Revision and to terminal 51 (or 51A) when using the internal 24VDC from
the panel on later Revisions.

5.

Multiple functions can be achieved by wiring multiple Auxiliary Inputs together. Ex. Auxiliary 1 and

Auxiliary 2 will start all the monitors Oscillating and Open the Water valves. To accomplish this wire
terminals 73 to 74 and one side of the normally open pushbutton and 24VDC for the original OCP
Revision and to terminal 51 (or 51A) when using the internal 24VDC from the panel on later Revisions.