Warning – Elkhart Brass SPIT-FIRE 8394053 Monitor User Manual

Page 4

Advertising
background image

4

I

OVERVIEW

NOTE TO ALL USERS:

• This manual was written with a dual monitor Operator Control Panel in most pictorial representations.

However a single monitor Operator Control Panel functions are handled identical that of the dual. All
information provided is applicable for both styles of Operator Control Panels.

• It should also be noted that the notation for Foam Valve has been changed to Auxiliary (Aux. Device on

the Panel) Device. The two are interchangeable and function the same way depending on which version
of OCP is being used. The name is the only difference.

Electrically Operated Remote/Local/Network Operator Control Panel (OCP) Features:

Construction – Stainless Steel enclosure rated for Hazardous Location (Class 1, Division 2).
Compliance – (NFPA 70) NEC: 2008, Article 501 – Class I, Groups “B, C, and D,” Division 2 and Article 505 –

Class I, Zone 2, AEx nA IIC T3 requirements; UL Labeled.

Control Power – 1/0 (On/Off) 2-Position selector switch.
Pilot Lights – Power On, Water Valve Open, Aux. Device On or Foam Valve On,

Parked, and Oscillation On

functions.

Internal Power – 24 VDC Power Supply for controls.
Controls – NEMA 4 (IP-66) controls. Joystick controls for monitor and nozzle movement (UP, DOWN, LEFT,

RIGHT, STRAIGHT STREAM, and FOG) and pushbutton controls for Park, Oscillation ON/OFF, Water Valve
OPEN/CLOSE and Aux. (Auxiliary) Device ON/OFF or Foam Valve OPEN/CLOSE.

Conduit Knockouts, Hubs, and external wiring – Supplied by others.
All incoming panel power, disconnect means, and lockout devices – Supplied by others.

WARNING:

Do not take cover off the Nozzle Motors. If cover is/has been removed, the

warranty is void and the service life of the motor is significantly reduced.

Definitions

Monitor Motor Control Panel (MMCP) – This panel is the relay interface from the Local or Network
Panel and the monitor. This panel is physically located between the Local or Network Panel and the
monitor. This panel has only a Power On/Off switch and a Power On indicator light. Depending on the
system this panel can also control Water and Foam Valve or Auxiliary Device ON/OFF operation.

Operator Control Panel (OCP) – This panel is a universal panel that depending on how it is configured or
used can be set up in multiple combinations to achieve multiple system configurations. Once programmed
it becomes a Remote or Local Operator Control Panel. This panel can be a two monitor or a one monitor
control panel. All operation and programming are identical.

Local Operator Control Panel (LOCP)
– This panel, either a dual or single, will be hardwired directly to
one or two MMCPs. It has a selector switch for Power On/Off and also the following pushbuttons for
Monitor Park, Monitor Oscillate On and Off, Water Valve Open and Close, and Foam Valve Open and
Close or Auxiliary Device On and Off. It includes a two position joystick for Nozzle Fog (wide spray
pattern) to Straight Stream (narrow spray pattern) and a four position joystick to move the Monitor
Up/Down or Left/Right. Only one movement can be achieved at a time per joystick. Indicator lights
include Power On, Oscillation On, Water Valve Opened, Foam Valve Opened or Auxiliary Device On, and
Parked. Each panel has a set of the above controls for one or two monitors.

Advertising