At the ROCP with water flowing out of the nozzle
and the Water Valve Opened light is not on

• Check for a burned out bulb
• Check that the networked LOCP water valve open

light is on

• Check that the jumper is in place at terminals 67 to

71

At the ROCP with foam flowing out of the nozzle
and the Foam Valve Opened or Auxiliary Device
ON light is not on

• Check for a burned out bulb
• Check that the networked LOCP foam valve open or

Auxiliary Device ON light is on

• Check that the jumper is in place at terminals 69 to

72

At the LOCP with a monitor oscillating the
indicator light is not on

• Check for a burned out bulb

At the ROCP with a monitor oscillating the
indicator light is not on

• Check for a burned out bulb
• Check that the networked control panels have the

same Monitor ID number (Section 4)

Park Light continually flashes quickly

• This is an indication that the monitor needs to be

calibrated and parked. Pressing the Park button will
cause the monitor to calibrate and the Park light will
flash slowly until the operation has completed.
Once the park procedure has been completed the
light will remain on until the monitor is moved from
the ROCP or LOCP by a joystick movement or by
starting oscillation.


Please refer to our website at

www.elkhartbrass.com

for any further information. Any problems that

cannot be fixed/solved should be taken to your Elkhart Brass Representative.