Determining cable lengths using the example table

Example: 6 switches are to be used in series. Cabling with a length of 40 m is

routed from a safety relay in the control cabinet to the last switch (#6). Cables with a

length of 20 m each are connected between the individual CES-AR safety switches.

Figure 1: Circuit example with six CES-AR

A safety relay is connected downstream which consumes 75 mA at each of the

two safety inputs. This operates over the whole temperature range with a voltage

of 19.2 V (corresponds to 24 V -20%).
All the relevant values can now be determined using the example table:
1. Select the corresponding section in the column n (max. number of switches).

Here: 6 switches.

2. In column I

out

(possible output current per channel OA/OB), find a current

greater than or equal to 75 mA. Here: 100 mA.

¨

It is then possible to determine the maximum cable length from the last switch

(#6) to the control system from column l

1

. Here: a length of 50 m is permitted.

Result: The desired cable length l

1

of 40 m is below the permitted value from the

table. The overall length of the switch chain l

max

of 140 m is less than the maximum

value of 200 m.

¨

The planned application is therefore functional in this form.

CES-AR # 6

Sicherheits-

relais

Safety Relay

CES-AR # 5

CES-AR # 4

CES-AR # 3

CES-AR # 2

CES-AR # 1

l

1

= 40 m

l

2

= 5 x 20 m

l

max

= 140 m

l

n

= 20 m

u

n

= min. 19,2 V

i

out

= min. 75 mA