Setup, Led indicators, Teach-in function for actuator – EUCHNER CES-AR-C01-AH-SA (Unicode) User Manual

Page 20: Setup 20 led indicators

Advertising
background image

Operating Instructions Safety Switch CES-AR-C01-AH-SA

20

Setup

LED indicators

LED

Color

State

Significance

STATE

green

illumi-

nated

Normal operation

flashing

- Teach-in operation or Power Up

- Actuator in limit range (V. 1.1.2 or higher)

(refer to the status table for further signal functions)

DIA

red

illumi-

nated

- Internal electronics fault

- Fault at the inputs/outputs

Teach-in function for actuator

The actuator must be allocated to the safety switch using a teach-in function before

the system forms a functional unit.
During a teach-in operation, the safety outputs and the monitoring output OUT are

switched off, i.e. the system is in the safe state.

Important!

Ì

The safety switch disables the code of the previous actuator if teach-in is
carried out for a new actuator. Teach-in is not possible again immediately for
this actuator if a new teach-in operation is carried out. The disabled code is
released again in the safety switch only after a third code has been taught.

Ì

The safety switch can only be operated with the last actuator taught.

Ì

If the switch detects the actuator that was most recently taught when in
teach-in standby state, this state is ended immediately and the switch chang-
es to normal state.

Ì

The actuator being taught is not activated if it is within the operating dis-
tance for less than 60 s.

Actuator teach-in

1. Apply operating voltage to the safety switch.

¨

The green LED flashes quickly (approx. 10 Hz)

A self-test is performed during this time (approx. 8 s). After this, the LED

flashes cyclically three times and signals that it is in standby state for teach-

in.

Standby state for teach-in remains active for approx. 3 minutes.

2. Move new actuator to the read head (observe distance < S

ao

).

¨

Teach-in operation starts, green LED flashes (approx. 1 Hz). During teach-in,

the safety switch checks whether the actuator is a disabled actuator. If this is

not the case, the teach-in operation is completed after approx. 60 seconds,

the green LED goes out. The new code has been saved, the old code disabled.

3. To activate the new actuator code from the teach-in operation in the safety

switch, the operating voltage to the safety switch must then be switched off

for min. 3 seconds.