Instruction Manual

– Model CF2500/CF3500 Oil Burner

10

Form 6104 BCF-35-R0699

Wire the burner

Install the burner and all wiring in accordance with the
National Electrical Code and all applicable local codes or
requirements.

Wire the burner in compliance with all instructions provided
by the appliance manufacturer. Verify operation of all controls
in accordance with the appliance manufacturer's guidelines.

See

Figure 10

for a typical wiring diagram for a CF2500A

Do not by-pass any safety control. By-passing a safety control could result in severe personal injury, death or
substantial property damage.

burner, with R8184 oil primary, for reference purposes only.
The CF2500/CF3500A burner is available with many different
wiring configurations. Refer to the wiring diagram shipped
with the burner for the actual wiring applying to your burner.

When firing over 20 GPH, the CF2500 and CF3500A will be
supplied with a flame safeguard control. An airflow switch
and low-fire start switch may also be supplied. Consult local,
state and federal codes for burner requirements above 20 GPH.

Legend

FD

Fused disconnect, by others

LM

Limit controls, by others

O P

Operating controls, by others

P R

Oil primary control, R8184 typical

CC

Flame sensor, cad cell typical

TM

Optional delay timer

TR

Ignition transformer

M1

Burner motor

S1

Primary oil valve

S2

High-fire valve

S3

Redundant oil valve

DM

Damper motor and end switch

∗∗∗∗∗

H/L

Insert high/low-fire control here

LFHS

Low-fire hold switch

T–T

24-volt thermostat/limit terminals

F-F

Cad cell flame sensor terminals

Electrical shock hazard - can cause
injury or death. Disconnect power before
installing or servicing. Provide ground
wiring to the burner in accordance with
the National Electrical Code.

Figure 10 – CF2500A Typical wiring

Note 1

Indicates alternate wiring for in-

terrupted ignition controls — connect
transformer to blue primary lead. For in-
termittent duty — connect transformer to
orange primary lead only.

BK

T

T

OR

F

F

WH

H

N

G

OR

OR

WH

WH

WH

WH

BR

BL (Note 1)

R

B

W

TR

TM

FD

PR

Power supply
120v/60 hz

S3

S1

DM

CC

LFHS

H/L

S2

DM

M1

LM

OP

BK = black

OR = orange

WH = white

Motor M1 wiring 14 ga All other wiring 16 ga

3514

Field wiring

Factory wiring

T

BL

BL = blue

BR = brown/red