Instruction manual, Verify firing rate, Verify air tube – Beckett CF 2500/ 3500 User Manual

Page 5

Advertising
background image

Instruction Manual

– Model CF2500/CF3500 Oil Burner

5

Form 6104 BCF-35-R0699

3502

E

D

G

F

T

1

Table 2 – Air tube capacity vs. firebox pressure

Figure 2 – Air tube mounting dimensions

E Insertion depth
G Air tube to inside of chamber

– 0.25" ± 0.125"

T Air tube length
D Tube diameter

Figure 1 – Min. combustion chamber dimensions

Install the burner with a 2° pitch as shown.

Verify firing rate

• Refer to appliance manufacturer’s instructions (if avail-

able) for firing rate and nozzle selection. Otherwise, the
maximum recommended firing rate for the burner depends
on the length of the firing chamber and the distance from
the burner center to the chamber floor. Verify that the cham-
ber dimensions are at least as large as the minimum values
given in

Figure 1

. If the appliance dimensions are smaller

than recommended, reduce the firing rate accordingly.

Verify air tube

• The information in this section may be disregarded if the

air tube is supplied by the appliance manufacturer.

• The following tube arrangements are available:

Model CF2500A

: Tube

KP

— 17.0 to 19.9 GPH

Model CF2500

:

Tube

KP

— 17.0 to 25.0 GPH

Model CF3500A

: Tube

KM

— 17.0 to 35.0 GPH

or

Tube

KR

— 17.0 to 35.0 GPH

• Maximum firing capacity depends on the firebox pressure.

Use

Table 2

to verify the correct air tube type for the firing

rate required. (Tube

KR

[

CF3500A

] is an optional air tube

combination for maximum capacity rate. It requires a larger
I.D. flange No. 51631.)

• See

Figure 2

to verify the correct air tube length and air

tube combination code.

3501

A

L

Firing rate

Minimum dimensions

(all boilers)

A

L

17 gph

10.5"

48.0"

22 gph

11.5"

58.0"

27 gph

12.5"

66.0"

32 gph

12.5"

73.0"

35 gph

13.0"

77.0"

A.T.C. Codes

(A.T.C. = Air Tube Combination)

CF2500A/

CF2500

CF3500A

Tube KP

Tube KM

Tube KR

Dimensions

Dimensions

Dimensions

T

D

F

T

D

F

T

D

F

All — 6 ½"

3¼"

All —

8"

4 ½" All — 9

¹⁵⁄₁₆

" 5

¹⁄₈

"

6¾"

CF 66 KP

8"

CF 80 KM —

9 ¼"

CF 92 KM —

10¼" CF 102 KP

11 ½" CF 114 KM 11 ½" CF 114 KR

13¾" CF 136 KP

15"

CF 150 KM 14"

CF 140 KR

17¾" CF 176 KP

19"

CF 190 KM 19"

CF 190 KR

Firebox

pressure

(In. W.C.)

Tube KP

Tube KM/KR

No

reserve

air

10%

turndown

No

reserve

air

10%

turndown

Maximum firing rate GPH

0.0

25.0

22.5

35.0

31.5

0.2

24.8

22.3

33.5

30.2

0.4

24.6

22.3

32.0

28.8

0.6

24.5

22.1

30.2

27.2

0.8

24.3

21.9

28.8

25.9

1.0

24.1

21.7

27.1

24.4

Note: 10% turndown indicates sufficient reserve air to reduce

the CO

2

in the flue to 90% of its value.

Note: The above ratings may vary 5% due to variations in actual job

conditions.