Prepare the burner for start-up

- continued

Z dimension

• Should be set per these instructions (see page 7). The top

acorn nut (

Figure 11

, item

d

) should never be loosened

once the

Z

dimension is initially set.

Adjusting plate assembly

(Figure 11)

• Make sure spline nut (item

b

) and bottom acorn nut (item

c

) are loose.

Initial head position

(Figure 11)

• The indicator plate assembly (item

e

) markings correspond

to head position settings.

• Slide the secondary adjusting plate (item

f

) toward the rear

of the burner until the number on the indicator plate corre-
sponds to the initial head setting given in

Table 4

for the

desired firing rate (high-fire).

Figure 11

shows a typical example, with a head setting of

5

.

• When the head position has been set, tighten the bottom

acorn nut (item

c

) and the spline nut (item

b

).

Initial air settings

(Figure 12)

• Loosen the screw holding the air adjusting plate (item

m

).

Set the air to the desired low-fire rate. (The numbers on this
plate correspond to the approximate firing rate settings
given in

Table 5

.)

• Rotate the air adjusting plate until the lower edge of the

pointer is opposite the number from

Table 5

corresponding

to the desired low-fire rate.

• This initial setting should be adequate for starting the

burner at low fire. Once the burner is in operation, the air
setting will be adjusted for best performance as discussed
later in this manual.

• The damper moves to high-fire position as the damper rod

(item

d

) rotates the damper linkage arm (item

f

). You will

adjust the setting of the damper linkage arm when setting
the high-fire air as discussed on page 14 in

Start the

burner

.

• Follow the procedures given later in this manual for fine

tuning the air settings.

Set appliance limit controls

• Set the appliance limit controls in accordance with the

appliance manufacturer's recommendations.

• Move the low-fire hold switch (not shown) to the “

IN

position. This will hold the burner in low fire during initial
start-up.

Legend

b Spline nut for securing nozzle line
c

Bottom acorn nut (for head adjust-

ments

d Top acorn nut (for setting dim. Z only

do not loosen after setting Z)

e

Indicator adjusting plate

Figure 11 – Adjusting plate initial setting, typical

f

Secondary adjusting

plate

g

Primary adjusting

plate

h Copper oil line from

oil valve to nozzle line

Table 4 – Initial indicator adjustment plate

settings (head position)

Prepare the fuel unit for air venting

• To vent air from one-pipe oil systems, attach a clear hose to

the vent plug on the fuel unit. Provide a container to catch
the oil. Loosen the vent plug.

• Vent the air as described under

Start the burner

, page 14.

3515

e

g

d

f

b

h

c

Approximate

head settings

Firing rate, gph

Tube “KP”

Tube “KM”/“KR”

0

--

--

1

--

17.00

2

--

17.50

3

17.00

18.00

4

17.50

18.50

5

18.00

19.00

6

18.50

20.00

7

19.00

21.00

8

20.00

28.00

9

21.00

32.00

10

25.00

35.00