TABLE 7.1: SUMMARY OF HORIZONTAL VENTING OPTIONS

VENT OPTION #

1

2

3

4

CLASSIFICATION USED IN THIS
MANUAL

HORIZONTAL
CONCENTRIC

HORIZONTAL

TWIN PIPE

(RESERVED

FOR FUTURE

USE)

(RESERVED FOR

FUTURE USE)

ILLUSTRATED IN FIGURE

7.2

7.3

VENT PIPE STRUCTURE
PENETRATION

WALL

WALL

AIR INTAKE PIPE STRUCTURE
PENETRATION

WALL

WALL

VENT PIPE SIZE

60/100 mm

CONCENTRIC

3”

AIR INTAKE PIPE SIZE

3”

MAXIMUM LENGTH

VENT

FCM070

32ft

55ft

FCM090

32ft

55ft

FCM120

18ft 55ft

INLET

FCM070

32ft

55ft

FCM090

32ft

55ft

FCM120

18ft

55ft

MINIMUM LENGTH

VENT

FCM070

10in

2ft

FCM090

10in

2ft

FCM120

10in

2ft

INLET

FCM070

10in

2ft

FCM090

10in

2ft

FCM120

10in 2ft

VENT TERMINAL

60/100 mm

CONCENTRIC

P/N 8110701

AIR INTAKE TERMINAL

3” 90 ELBOW

VENT MATERIAL

U.S. Boiler

60/100mm

VENT

COMPONENTS

SHOWN IN

TABLE 7.4

(Note #1)

APPROVED

STAINLESS

STEEL VENT

SYSTEM

SHOWN IN

TABLE 7.5

AIR INTAKE MATERIAL

GALVANIZED

OR PVC

Note #1: The 80/125mm concentric straight section (P/N 101162-01) shown in Table 7.4 may be used between the boiler and the fi rst 80/125 x 60/100 reducing

elbow. If this is done, the overall maximum vent length is still restricted to that shown for Vent Option #1 in Table 7.1 above.