TABLE 4.2: CLEARANCES FROM VENT PIPING TO COMBUSTIBLE CONSTRUCTION

TYPE OF VENT PIPE

PIPE DIRECTION

ENCLOSURE

MINIMUM CLEARANCE

TO COMBUSTIBLE

MATERIAL

60/100mm

CONCENTRIC VENTING

VERTICAL OR

HORIZONTAL

ENCLOSED ON ALL FOUR SIDES

0”

HEAT FAB SAF-T VENT

PROTECH FASNSEAL

Z-FLEX Z-VENT III

FLEX-L STAR-34

VERTICAL OR

HORIZONTAL

AT LEAST ONE SIDE OPEN,

COMBUSTIBLE MATERIAL ON A

MAXIMUM OF THREE SIDES

1”

HEAT FAB SAF-T VENT

PROTECH FASNSEAL

Z-FLEX Z-VENT III

FLEX-L STAR-34

HORIZONTAL OR VERTICAL

WITH OFFSETS

ENCLOSED ON ALL FOUR SIDES

2-1/2”

HEAT FAB SAF-T VENT

PROTECH FASNSEAL

Z-FLEX Z-VENT III

FLEX-L STAR-34

VERTICAL WITH NO OFFSETS

ENCLOSED ON ALL FOUR SIDES

2-1/2”