TABLE 9.6: PIPE AND CIRCULATOR SIZING FOR INDIRECT WATER HEATER LOOP

BOILER

MODEL

(a)

(b)

(c)

(d)

(e)

(f)

PIPE

SIZE

FLOW

MAX. I.W.H.

PRESSURE

DROP

ALLIANCE™

INDIRECT WATER

HEATERS

CIRCULATOR

MODEL

I.W.H. LOOP MAX

EQUIVALENT

LENGTH

(in NPT)

(GPM)

(ft HEAD)

(ft)

FCM070

1

6.0

1.7

AL27SL (*)
AL35SL (*)
AL70SL (*)
AL119SL (*)

Taco 008

102

FCM090

1

8.0

3.0

AL27SL, AL35SL

AL50SL (*)
AL70SL (*)
AL119SL (*)

Taco 0014

50

FCM090

1

8.0

3.0

AL27SL, AL35SL

AL50SL (*)
AL70SL (*)
AL119SL (*)

Taco 0013 (Note #3)

190

FCM120

1

8.0

3.0

AL27SL
AL35SL
AL50SL
AL70SL

AL119SL

Taco 0014

71

FCM120

1

8.0

5.0

AL27SL, AL35SL
AL50SL, AL70SL

AL119SL
(Note #2)

Taco 0014

45

FCM120

1

8.0

5.0

AL27SL, AL35SL

AL50SL , AL70SL

AL119SL
(Note #2)

Taco 0013 (Note #3)

185

NOTES:

1) Indirect water heaters with an asterisk (*) will not achieve their catalog rating due to inadequate boiler water fl ow and/or inadequate boiler

output.

2) When used with an indirect heater having a pressure drop less than 3.0 ft of head, the Taco 0013 can be installed with up to 211 equivalent ft of

1” pipe.

3) Use isolation relay between Taco 0013 and FCM - see Figure 10.3

TABLE 9.5: PIPE AND CIRCULATOR SIZING FOR BOILER LOOP

BOILER

MODEL

(a)

(b)

(c)

(d)

(e)

PIPE

SIZE

FLOW

TEMP

RISE

CIRCULATOR

MODEL

BOILER LOOP

MAX EQUIVALENT

LENGTH

(in NPT)

(GPM)

(F)

(ft)

FCM070

1

6.0

22

Taco 007

55

FCM070

1

6.0

22

Taco 008

145

FCM090

1

8.0

21

Taco 0014

90

FCM090

1

8.0

21

Taco 0013 (Note #1)

230

FCM120

1

8.0

29

Taco 0014

111

FCM120

1

9.0

25

Taco 0014

61

FCM120

1

12.0

19

Taco 0013 (Note #1)

28

NOTE: 1) Use isolation relay between Taco 0013 and FCM - see Figure 10.3