XTC/C - XTC/2 Operating Manual

As illustrated in

Figure 5-7 on page 5-13

, the control dead time, L, is the time

delay between a change in the source’s power setting and a noticeable change
in deposition rate. The control time constant, T

1

is (T

0.632

- L) where T

0.632

is

the time between a change in the source’s power setting and the time to
achieve 63.2% of the new equilibrium rate.

K

P

is then the ratio of the change in rate over the change in source power

setting.

[1]

These values may be adjusted slightly in use to optimize the tuning. The tuning
may change because of process variations. Usually CTL TC and CTL DT do
not need to be changed.

NOTE: Remember that increasing the value of CTL GAIN reduces the

controller change for a given rate error.

Figure 4-7 Examples of Delay Settings

K

p

(change in output)

(change in control signal)

-------------------------------------------------------------------

Å sec

%Pwr

---------------------

=

=