Local lockout mode activation, Remote lockout mode activation, Short circuit and overload protection – Johnson Systems CS-DMX Series Programmable Stations User Manual

Page 10

Advertising
background image

www.johnsonsystems.com

10

Local Lockout Mode Activation

When the local lockout mode is activated, the control station is locked in the “OFF” state.

Any button press is ignored and the “OFF” LED flashes once to indicate local lockout mode is

activated.
Procedure:

• To activate the local lockout mode, press and hold the “OFF” button for approximately

10 seconds, until the “OFF” LED extinguishes.

• To deactivate the local lockout mode, press and hold the “OFF” button for approximately

10 seconds, until the “OFF” LED illuminates.

Remote Lockout Mode Activation

When the remote lockout mode is activated, the control station ignores all remote control station

key presses. The active LED flashes off for 0.1 seconds every 2 seconds to indicate remote

lockout mode is activated.
Procedure:

• To activate the remote lockout mode, press and hold the “DIM” button for approximately

10 seconds, until the “DIM” LED flashes off for 0.1 seconds.

• To deactivate the remote lockout mode, press and hold the “DIM” button for approximately

10 seconds, until the “DIM” LED flashes off for 0.1 seconds.

Short Circuit and Overload Protection

The control station is equipped with short circuit and overload protection. The short circuit limit is

set at 100mA with 0.6W of power dissipation. When a short circuit or overload is detected while in

the “ON” or “DIM” state, all of the button LED’s flash on and off to indicate there is a short circuit

or overload condition. The control station automatically recovers to normal operational state once

the short circuit or overload is removed.