Hand-held programmer, Mounting the control station, Calibrate the dmx output range – Johnson Systems CS-DMX Series Programmable Stations User Manual

Page 8

Advertising
background image

www.johnsonsystems.com

8

COM
V+
ON
DIM
RST

CS-DMX-12

DC POWER SUPPLY COMMON (V-) INPUT
DC POWER SUPPLY POSITIVE (V+) INPUT

COM
V+

DMX OUT

CS-DMX-12

DMX OUT

DMX IN

COM
V+
ON
DIM
RST

Wiring Two or More Control Stations Together
with “Mimic”

“Mimic” refers to pressing a button (“ON”, “DIM” or “OFF”) on a control station, and the other

control station(s) are automatically triggered into the same “ON”, “DIM” or “OFF” state. The

analog output(s) could be controlling the same device or completely different device. Wiring

between the control stations requires 2 conductors for V+ and common, and 3 conductors

(2 conductors for Part Number: CS-SA-ENT2B) for the switches (ON, DIM and RST), 1 conductor

for each switch function. A DMX cable between the control stations is required, along with a DMX

cable from one of the master control stations to the DMX receiving device.

Mounting the Control Station

The control station can be mounted on/in a gangable (usually masonry) type of back box

with a minimum depth of 2" (50.8mm) and a preferred depth of 3.5" (88.9mm). A #2 Phillips

head screwdriver is required to secure the control station, using the provided black #6-32 x 1"

(25.4mm) mounting screws.
NOTE: Ensure the back box is earth grounded to protect the control station from electrostatic

discharge.

NOTE: Ensure the back box mounting-hole threads are not damaged. Damaged threads on the

back box can damage the threads on the mounting screws and cause stripping. The back

box threads can quickly be cleaned up by running a #6-32 tap through the mounting hole.

Be sure not to over-tighten the mounting screws or this could result in stripping the back

box mounting-hole threads.

Calibrate the DMX Output Range

All CS-DMX Series control stations are factory calibrated for 0-100% DMX control with a 10.6VDC

to 18VDC power supply. If the control station does not have a full range of DMX control, please

consult a factory representative.

Configure the Control Station Using a CS-IPRO
Wireless Hand-Held Programmer

To configure the control station, a Johnson Systems Inc. Model Number: CS-IPRO wireless hand-

held programmer is required. The CS-IPRO is required primarily to configure the DMX channel

patch for each of the sliders, however, it provides several other useful features.
Wireless communication between the CS-IPRO and CS-DMX Series control stations is via

bidirectional infrared LED’s. The control station infrared LED window is located between the

master (M) slider and slider 1. The maximum range for sending and receiving data between the

control station and CS-IPRO is 12" (30cm).
NOTE: Refer to the CS-IPRO user manual for detailed programming information.