51

7 Data transfer to device

TCP/IP PORT

The following parameters must be selected.

Analog modem /
ISDN

The following parameters must be selected.

IP address /
HOST name

xxx.xxx.xxx.xxx
(Example: 10.11.2.100
or Hall1-Furnace1)

Enter the IP address of
your PC. If you enter the
name, the IP address
can be determined by
clicking on the button
“Convert HOST name to
IP address”.

Port number,
port name

502

The port used for
communication.

Communication
protocol

Modbus TCP/IP,
Modbus protocol

Set the
Modbus TCP/IP
here.

Device address

1 — 255

Device address for the
Modbus protocol.
The parameter is not
required for Modbus
TCP/IP.

Telephone number

Enter the telephone
number for connection
to the required device.

Connect via

Select the modem that
is to be used to make
the connection.

Communication
protocol

Modbus TCP/IP,
Modbus protocol

Set the
Modbus protocol
here.

Device address

1 — 255

Device address for the
Modbus protocol.
The address must
match the device
address that was set on
the device or in the
setup program.