Chapter

4

Setup
Procedure






A complete listing of a sample ladder logic program is included at the back of this manual.
Examples shown here are for reference.



All values are 0 (default) on initial start-up. This means that all alarms are
disabled. You must make the following adjustments for proper operation:

Balance sensor input(s)

Set Calibration numbers



Step 1. Balance Sensor Input.

1. Set mV/V to 2000.

2. Set Scale to 10000.

3. Press Clear Tare pushbutton.

4. Use Up and Down buttons to set amplifier to low range of A/D (20,000 counts)

5. Press Zero/Tare pushbutton.

Step 2. Set Calibration Numbers

1. Set Scale to capacity of load cell.

2. Set mV/V to load cell specification.

3. Example:

100 ton load cell, 2.025 mV/V

For scale set, enter 100

For mV/V set, enter 2025














Page 4-1