7 configuration level – JUMO 14597 safetyM TB/TW - Temperature Limiter and Temperature Monitor Operating Manual User Manual

Page 24

Advertising
background image

7 Configuration level

2014-06-12

22

k

Factory setting

037

W3Re-W25Re D

Thermocouple

-1999 to +9999°C

-5 to +2500°C

039

Cu-CuNi T

Thermocouple EN 60584

-1999 to +9999°C

-205 to +405°C

040

Fe-CuNi J

Thermocouple EN 60584

-1999 to +9999°C

-205 to +1205°C

041

Cu-CuNi U

Thermocouple DIN 43710

-1999 to +9999°C

-205 to +605°C

042

Fe-CuNi L

Thermocouple DIN 43710

-1999 to +9999°C

-205 to +905°C

043

NiCr-Ni K

Thermocouple EN 60584

-1999 to +9999°C

-205 to +1377°C

044

Pt10Rh-Pt S

Thermocouple EN 60584

-1999 to +9999°C

-5 to +1773°C

045

Pt13Rh-Pt R

Thermocouple EN 60584

-1999 to +9999°C

-5 to +1773°C

046

Pt30Rh-Pt6Rh B

Thermocouple EN 60584

-1999 to +9999°C

295 to 1825°C

048

NiCrSi-NiSi N

Thermocouple EN 60584

-1999 to +9999°C

-105 to +1305°C

052

0 to 20 mA

-1999 to +9999°C

0 to 21mA

053

4 to 20 mA

-1999 to +9999°C

3.6 to 21mA

063

0 to 10 V

-1999 to +9999°C

0 to 10.5 V

071

2 to 10 V

-1999 to +9999°C

1.8 to 10.5V

v

Chapter 10.4 “Restricting the setting

range for the AL limit (minimum/maximum
value master)”

Analog input

Comment

Setting range for AL:
(can be restricted via
setup)

Limits for
overrange/
underrange

Advertising