13 what if – JUMO 14597 safetyM TB/TW - Temperature Limiter and Temperature Monitor Operating Manual User Manual
Page 49
Advertising
13 What if...
47
Description
Cause
Remedy
Relay contact between
terminals 9, 10 or 9, 12
does not switch.
-
The fitted safety fuse in the pole arm 9 is
faulty.
h
Measure terminals 9 and 10 of the relay with
a continuity tester when LED K1 shows
green.
h
Measure terminals 9 and 12 of the relay with
a continuity tester when LED K1 is off
h
The instrument must be returned to JUMO
for repair.
v
Chapter 2.1 “Service addresses”
Double LED lit (green and
red simultaneously)
-
Internal system error
- Switch the supply off and then back on again
If this does not help, the instrument must be
returned to JUMO for repair.
v