8 technical data – JUMO 14597 safetyM TB/TW - Temperature Limiter and Temperature Monitor Operating Manual User Manual

Page 33

Advertising
background image

8 Technical data

31

2014-06-12

DC voltage, DC current

NiCrSi-NiSi N

EN 60584

-100 to +1300°C

0.4%

Pt10Rh-Pt S

EN 60584

0 to +1768°C

0.4%

Pt13Rh-Pt R

EN 60584

0 to +1768°C

0.4%

Pt13Rh-Pt6Rh B EN 60584

300 to 1820°C

0.4%

W3Re-W25Re D

0 to +2495°C

0.4%

Cold junction

Pt 100, internal

Cold junction accuracy

± 1K

Sampling

210 ms

Input filter

2nd order digital filter; filter constant adjustable from 0 to 100secs

Features

also programmable in °F

1. Accuracy refers to the maximum extent of the measuring range.

Measuring range

Accuracy

0 to 20mA, voltage drop < 2 V
4 to 20mA, voltage drop < 2 V

0.2%

0 to 10V, input resistance > 100 k

Ω

2 to 10V, input resistance > 100 k

Ω

0.1%

Scaling

freely programmable within the limits

Sampling time

210 ms

Input filter

2nd order digital filter; filter constant adjustable from 0 to 100secs