Wiring the device modules

Safety modules

8

l

81

EDK94ASH24 DE/EN/FR/ES/IT 4.1

Terminal assignment

)

Note!

Provide for a sufficient strain relief, so that the terminals are not pulled from
the plug connectors, in particular when you use rigid cables.

X82.1

Labelling

Description

This part of the terminal strip is not assigned.

GO

GND SD−Out1

O1B

Safe monitor SD−Out1, channel B

O1A

Safe monitor SD−Out1, channel A

This part of the terminal strip is not assigned.

X82.2

Labelling

Description

GND external supply

+

+24 V external supply via a safely separated power supply unit (SELV/PELV)

GIR

This part of the terminal strip is reserved.

RI1

GO

GND 24O

24O

+24 V external supply for the safe monitor SD−Out1 (SELV/PELV)

AIE

Error acknowledgement input ("Acknowledge In Error")

CLA

Clock output for passive sensors, channel A (Clock A)

CLB

Clock output for passive sensors, channel B (Clock B)

X82.3

Labelling

Description

GCL

GND clock output

GI2

GND SD−In2

I2B

Sensor input SD−In2, channel B

I2A

Sensor input SD−In2, channel A

GCL

GND clock output

GI1

GND SD−In1

I1B

Sensor input SD−In1, channel B

I1A

Sensor input SD−In1, channel A

AIS

Restart acknowledgement input ("Acknowledge In Stop", 1−channel,
bridged to X82.4/AIS)