Step, Model 530 operating instructions, Ez-step™ size and direction cont – Practical Instrument Electronics 530 User Manual

Page 3: Auto step/ramp, Quick reference bar graph

Advertising
background image

Model 530 Operating Instructions

EZ-Step™ Size and Direction cont.

To Change the EZ-Step

TM

Direction:

1. Press the EZ-Dial knob.

2. The display will change to show the EZ-Step

TM

direction selected (

or

).

Auto

Step/Ramp

Auto step/ramp times are given in Table 1. In step modes (EZ-Step sizes 8, 4, and 1 mA or 50, 25 and

10 %) the output will change in discrete steps. In ramp modes, the output is approximately continuous.

Table 1 assumes the default EZ-Check LO/HI of 4/20 mA and scales ratiometrically with the EZ-Check

span. Soak Time does not change with EZ-Check span.

The Model 530 will detect high loop resistance/low supply in step modes. In ramp modes, these error
conditions are not detected.

Table 1

Auto EZ-Step Size

Step Time

Ramp Time

(4-20 mA or 0-100 %)

Soak Time

8.000 mA

50.00 %

10 seconds

(30 seconds)

20 seconds

4.000 mA

25.00 %

10 seconds

(50 seconds)

20 seconds

1.00 mA

1.9 seconds

(34 seconds)

3.8 seconds

Step

10.00 %

1.8 seconds

(21 seconds)

3.6 seconds

1.00

%

20 seconds

0.10

%

25 seconds

0.100 mA

32 seconds

0.010 mA

40 seconds

0.01

%

83 seconds

Ramp

0.001 mA

134 seconds

Quick Reference Bar Graph

The Quick Reference Bar Graph indicates the input and output level to the Model 530 in % of 4-20 mA

with 1% resolution. If the input or output signal is outside the normal operating range of the Model 530
the Quick Reference Bar Graph is replaced by an error message (see section I for errors.)


Auto Off

-

ON

(default)/OFF

If Auto Off is ON, the unit will turn off after 30 minutes to save battery life, if there is no user activity. If

Auto Off is OFF the unit will stay on until it is turned off from the keypad. This is typically useful for
manual loading or continuous use.


EZ-Step
-

ON/OFF

(default)


If EZ-Step is ON the step size is adjustable as described in the instructions. If EZ-Step is OFF the EZ-
Step pushbutton will be disabled and the step direction indicator will not be displayed.




841 Holt Road #1 Webster, NY 14580

Tel: 585-872-9350 Fax: 585-872-2638

[email protected] http://www.piecal.com/

Practical Instrument Electronics, Inc. Copyright 2002. All rights reserved.

530-9002 2/26/04

3-8