Inspection frequency and items, Maintenance and inspection, Maintenance contract – RKI Instruments SD-705EC User Manual

Page 19

Advertising
background image

PT2E-1140

4.

Maintenance and Inspection

The gas detection alarm is kept in continuous operation over a long period of time and must
perform a vital role as a safety device. For this purpose, periodical inspection must be made.
The High-pressure Gas Safety Act in Japan sets forth the obligation of periodical inspection of
the gas detection alarm.

-Maintenance Contract-

☆ To maintain the safety operation of detector, it is recommended to keep the

maintenance contract with service agent for regular maintenance, adjustment and

overhaul etc. including the gas sensitivity adjustment.
For the detail of maintenance contract, contact nearest agent.








4−1 Inspection Frequency and Items

The inspection includes a daily inspection which a person in charge of control and operation of
the gas detection alarm performs inspection before work once a day, and periodical inspections
conducted by the service personnel of a manufacturer. The inspection items are confirmation
of the concentration indication on the detector side and confirmation of lights, concentration
indication and alarm function on the indicating alarm side. It is also necessary to carry out gas
calibration at least every 6 months. The law sets forth that the unit must issue the alarm
during the circuit inspection related to alarm while providing normal operation, at least, once a
month.

Contents of inspection

Inspection

Point/item

Daily inspection

Monthly inspection

Judgment

Status light

check

Check if the

“PW/TR” LED
light(power light)
is ON.

Brightness of
“PW/TR” LED light
is good.

The “PW/TR” LED light must be ON. If
flickering, take an appropriate measure
according to 5-2. Troubleshooting guide.

Gas consent.

indication

check

Check if the gas
consent. indication
of the indicator is
zero.

Same as daily

inspection

The gas concentration indication must be zero
in the clean atmosphere. If not, carry out zero
adjustment according to the zero adjustment
method.

Equipment

installation

state check

Check if there is any
obstruction for
detection of the gas
concerned.

Same as daily

inspection

No obstruction for gas detection. If any,
remove such obstruction or move the unit to
another place.

Sensor check

Check if the gas inlet
is covered with dust
or water or if it is
discolored.

Same as daily

inspection

No abnormality in gas inlet. If it is covered
with dust or water, remove and carry out zero
and span adjustments according to 4-4 Gas
Sensitivity Calibration Method. If cannot be
adjusted, consult with RIKEN KEIKI.

18