4−4 4mASignal Output Adjustment Method

① Press SET switch● in MENU display

② When signal output adjustment mode is entered is displayed on LCD,

and signal output becomes 4mA (value : zero).

③ Adjust indication value to 4mA(zero) on indication part* of DSC and etc which is

connected separately by pressing UP switch▲ and DOWN switch▼.

④ After adjustment, press SET switch● to decide. When it is decided, SPAN light is

lighting.

* : If indication value cannot be confirmed on indication part, signal output can be

confirmed by connecting a tester (Ammeter) to check pins between TP1(+) and

TP1(-).

4−5 Alarm Point Change Method


1

st

alarm and 2

nd

alarm can be alternated individually.

① Pres SET switch● in menu display

② When alarm set mode is entered, AL light is on and current 1

st

alarm value is displayed

on LCD.

③ When changing alarm point, press SET switch●。

④ Then, AL1 light is changed from lighting into flickering, and alarm point on LCD is

changing as same. Press UP switch▲ and DOWN switch▼ to adjust.

⑤ After adjustment, press SET switch● and return to ①

⑥ Then, press UP switch▲.

⑦ Current 2nd alarm point is displayed on LCD. And AL2 light is lighting.

⑧ 2

nd

alarm point can be changed as same as 1

st

alarm point.