SATEC EM720 Operation Manual User Manual

Page 104

Advertising
background image

Chapter 5 Configuring the EM720

Configuring Recorders

104

EM720 Power Quality and Revenue Meter

Data Log #2

No. Parameter

1 V1/V12

Demand

2 V2/V23

Demand

3 V3/V31

Demand

4 I1

Demand

5 I2

Demand

6 I3

Demand

7

kW Import Sliding Demand

8

kvar Import Sliding Demand

9

KVA Sliding Demand

10 kWh

Import

11 kWh

Export

12 kvarh

Import

13 kvarh

Export

14 kVAh
15 In
16 Frequency

Data Log #13

Data Log #13 is linked to the Fault recorder and is configured
for fast 1/2-cycle RMS profiling of fault events. You can freely
manipulate this file, as you want. See

Configuring the Fault

Recorder

in Chapter 5 on how to enable or disable RMS

profiling and how to define the maximum duration of the fault
RMS profiles.

The factory pre-configured list of parameters for Data log
#13 is shown in the following table.

Data Log #13

No. Parameter

1

1/2-cycle voltage V1/V12

2

1/2-cycle voltage V2/V23

3

1/2-cycle voltage V3/V31

4

1/2-cycle (neutral/zero-sequence) voltage V4

5

1/2-cycle current I1

6

1/2-cycle current I2

7

1/2-cycle current I3

8

1/2-cycle current I4

9

1/2-cycle zero-sequence voltage

Data Log #14

Data Log #14 is linked to the Power Quality recorder and is
configured for RMS profiling of power quality events. You can
freely manipulate this file. See

EN50160 PQ Recorder Setup

in Chapter 5 on how to enable or disable RMS profiling and
how to define the maximum duration and time envelopes for
the PQ RMS profiles.

The factory pre-configured list of parameters for Data log
#14 is shown in the following table. The time integration
interval for these parameters is dynamically changed as the
event continues for more time.