Configuring dnp3, Dnp options – SATEC EM720 Operation Manual User Manual

Page 121

Advertising
background image

Chapter 5 Configuring the EM720

Configuring Communication Protocols

EM720 Power Quality and Revenue Meter

121

4. Click Send to download your setup to the device.

Configuring DNP3

DNP Options can be changed both via DNP3 and Modbus.
Refer to the EM720 DNP3 Reference guide for information on
the protocol implementation and a list of the available data
points.

DNP Options

From the Meter Setup menu select Protocol Setup and click
on the DNP Options tab.

The following table describes available DNP options. Refer to
the DNP3 Data Object Library document available from the
DNP User’s Group on the DNP3 object types.

Parameter Options

Default

Description

Binary Inputs (BI)

Number of BI to Generate

events

0-64

3

21

The total number of BI change

event points for monitoring

Binary Input Object

Single-bit
With Status

Single-bit

The default BI object variation for
requests with qualifier code 06
when no specific variation is

requested

Binary Input Change
Event Object

Without Time
With Time

With Time

The default BI change event object
variation for requests with qualifier
code 06 when no specific variation

is requested

Analog Inputs (AI)

Number of AI to Generate
events

0-64

3

43

The total number of AI change
event points for monitoring