Using pas – SATEC EM720 Operation Manual User Manual

Page 131

Advertising
background image

Chapter 6 Device Control and Upgrading

Resetting Accumulators and Log Files

EM720 Power Quality and Revenue Meter

131

Access to the RESET menu entries is allowed depending on
your security level as shown in the following table. Clearing
files is not allowed from the front display.

Reset Entry

Menu Function

Security

Level

Diagnostics

Reset of device diagnostics

Low

Bill/TOU MD

Reset of billing maximum demands and triggering an

end of billing period

Low

Power MD
Volt/Amp MD
Volt MD
Ampere MD
Harmonic MD
All MD

Reset of engineering maximum demands

Low

Dev.Oper.Time Reset of the meter operation time counters

Medium

Lith.Bat.Time

Reset of the lithium battery operation time counters

Medium

Aux.Bat.Time

Reset of the rechargeable auxiliary battery operation
time counters

Medium

Power Failures

Reset of the meter failure counters

Medium

To reset a desired entry:

1. Use the SCROLL button to scroll through the menu

entries until a required reset entry appears in the
window.

2. Press briefly SELECT/ENTER button to highlight the

“Do” entry.

3. Press and hold the SELECT/ENTER button for more

than 5 seconds until the “Do” entry is replaced with
“Done” indicating that the operation is complete.

4. Release the button.

If your security level does not allow access to a menu entry,
you will not be able to highlight the lower action window.

NOTE

You may not be allowed to reset the billing maximum
demands in the event this action is not enabled for the front
display in the Device Options setup, or it has been just
performed once at the same day – the meter does not allow
repeated triggering an end of billing period within one
calendar day.

Using PAS

Select Reset from the Monitor menu.

Refer to the table above for required permissions. To clear
log files, you should have the administration rights.

NOTE

The “Clear All Log Files” entry does not affect billing data and
energy load profile files.

EXTENDED PRESS

ENTER

SHORT PRESS

SELECT

SCROLL

Advertising