SATEC PTS175 Manual User Manual

Page 12

Advertising
background image

‎Appendix A Technical Specifications

PTS175 MV Advanced Analyzer

12

Labels: Polycarbonate (UL94-V0)
Ingress Protection: IP65

A.3

Power Supply inputs

120/230 VAC-DC Input:

Rated input: 85-265VAC 50/60/400 Hz, 88-290VDC, Burden 9VA
Lightening withstanding: 10,000A

12 VDC Input:
Rated input: 12 VDC ± 10%, 10W
Lightening withstanding: 1000A

All Power supply sources must be grounded to earth

A.4

Input Ratings

Voltage Inputs
Primary Measuring range: 11-33 KVAC line-to-line, 6.35-20 KVAC line-to-neutral
Input impedance: 1000 k

Current Inputs
Primary Measuring range: up to 600A
Sampling Rate measurement
128 samples/cycle.

Lightening withstanding: 10,000A

A.5

Real-time Clock

Accuracy: typical error 1 minute per month @ 25

C

Typical clock retention time: 2 years

A.6

Standards Compliance

Accuracy:
Meet IEC62053-22, class 1
Electromagnetic Immunity:
Comply with IEC 61000-6-2:

IEC 61000-4-2 level 3: Electrostatic Discharge
IEC 61000-4-3 level 3: Radiated Electromagnetic RF Fields
IEC 61000-4-4 level 3: Electric Fast Transient

IEC 61000-4-5 level 4: Surge
IEC 61000-4-6 level 3: Conducted Radio Frequency

IEC 61000-4-8: Power Frequency Magnetic Field

Electromagnetic Emission:
Comply with IEC 61000-6-4: Radiated/Conducted class A
Comply with IEC CISPR 22: Radiated/Conducted class A
Safety/Construction:
Meets UL/IEC 61010

Advertising