Regency Freestanding Woodstove

8

INSTALLATION

MINIMUM CLEARANCE TO

COMBUSTIBLE MATERIALS

Please read the section below carefully as clearances depend on whether the airmate or the rear heat defl ector is installed on the stove.

Measurements "From Unit" are from the top plate of the stove to a side wall or to a corner, and from the rear heat shield to a back wall.

Mobile Home Close Clearance (To be installed with required pipe components)

"C" Vent single wall pipe is not approved for Mobile Home installations. (Refer to Mobile Home Instructions.)

Unit

From Unit From Corner From Flue Center-line

A B C D E F

Small F1100S

with Airmate

11"

6" 6" 23"

12.5" 18"

with Rear Defl ector

13"

5" 9" 25"

11.5"

21"

Large F3100L

with Airmate

18" 9.5" 10" 32" 16" 23.5"

with Rear Defl ector

20" 12" 10" 34" 18.5"

23.5"

NOTE: Be aware that local Codes and Regulations may override some clearances listed in this manual.

Check with your local inspector.

Residential Installation “C” Vent (Single Wall)

Unit

From Unit From Corner From Flue Center-line

A B C D E F

Small F1100S

with Airmate

13" 11" 8" 25" 17.5"

20"

with Rear Defl ector

15" 10.5"

11" 27" 17" 23"

Large F3100L

with Airmate

18" 12" 8.5" 32" 18.5"

22"

with Rear Defl ector

20" 14" 10.5"

34" 20.5"

24"

Residential Close Clearance (To be installed with required pipe components)

When the stove is installed as a close clearance residential unit, a listed double wall connector is required from the stove
collar to the ceiling level.

Unit

From Unit From Corner From Flue Center-line

A B C D E F

Small F1100S

with Airmate

9" 5" 3" 21"

11.5"

15"

with Rear Defl ector

13.5"

5" 5" 25.5"

11.5"

17"

Large F3100L

with Airmate

16" 9.5" 8.5" 30" 16" 22"

with Rear Defl ector

20" 12" 8.5" 34" 18.5"

22"