Installation, Aeration adjustment, Gas pipe pressure testing – Regency Hampton H27 Medium Gas Stove User Manual

Page 30

Advertising
background image

30

Hampton

®

H27 Direct Vent Freestanding Gas Stove

INSTALLATION

AERATION

ADJUSTMENT

The burner aeration is factory set but may need
adjusting due to either the local gas supply, air sup-
ply or altitude.

Natural Gas

3-16" (4.76 mm)

Propane

1/4" (6.4 mm)

The aeration adjustment gears are located on the
right side of the burner box. Remove the Hampton

®

Logo plate on the right side of the unit to access
the adjustment gears.

To adjust the aeration: use the allen key to turn

GAS PIPE

PRESSURE TESTING

The appliance must be isolated from the gas sup-
ply piping system by closing its individual manual
shut-off valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psig. (3.45 kPa). Disconnect piping
from valve at pressures over 1/2 psig.

The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.

Note: To properly check gas pressure, both

inlet and manifold pressures should be
checked using the valve pressure ports
on the valve.

1) Make sure the valve is in the "OFF" position.

2) Loosen the "IN" and/or "OUT" pressure tap(s),

turning counterclockwise with a 1/8" wide fl at
screwdriver.

3) Attach manometer to "IN" and/or "OUT" pres-

sure tap(s) using a 5/16" ID hose.

4) Light the pilot and turn the valve to "ON" posi-

tion. Read manometer.

5) The pressure check should be carried out with

the unit burning and the setting should be within
the limits specifi ed on the safety label.

6) When

fi nished reading manometer, turn off the

gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" fl at screwdriver.
Note: Screw should be snug, but do not over
tighten

Valve Description

the turning gear which will adjust the air shutter.
Open the air shutter for a blue fl ame or close it for
a more yellow fl ame. This adjustment is performed
by a qualifi ed installer. The factory setting should
be suffi cient for most installations.

Clockwise to open,

counter-clockwise to close.

Caution: Carbon will be produced if the air
shutter is closed too much.

Note: Any damage due to carboning resulting

from improperly setting the aeration
controls is NOT covered under warranty.

Note: Aeration Adjustment should only be

performed by an authorized Hampton

®

Installer at the time of installation or
service.

1) Gas on/off knob

2) Manual high/low adjustment

3) Pilot

Adjustment

4) Thermocouple

Connection

5) Main

Operator

6) Outlet Pressure Tap (Manifold Pressure)

7) Inlet Pressure Tap (Supply Pressure)

8) Pilot

Outlet

9) Main Gas Outlet

10) Flange Securing Screw Holes

11) Alternative TC Connection Point

12) Thermoelectric Unit

13) Additional Valve Mounting Hole

Advertising