18

Table 10a – MotorGuard Technical Specifications – General Purpose

Current ratings

Continuous current: 55 to 600 amps. See Rating and Dimension tables

Intermittent current: 150% for 1 minute out of every 60 minutes

VFD Drive output voltage

460/480 and 575/600 V, 3 ph, at fundamental base frequency

VFD Drive output
frequency

0 to 80 Hz

VFD Drive carrier
frequency

2 kHz and 12 kHz, Ideally 4 kHz to 8 kHz

Control power input

For fan operation.

Filter performance

Maximum peak voltage of output waveform – 480 V models: 1000 V

– 600 V models: 1500 V

Maximum dv/dt of output waveform – 480 V models: 500 V/

μs

– 600 V models: 1500 V/

μs

Maximum elevation

3,000 feet (1,000 meters) as standard. Product must be equipped with
special cooling provisions for operation above this level

Maximum ambient
operating temperature

40 °C (104 °F) as standard. Product must be equipped with special
cooling provisions for operation above this temperature.

Maximum ambient storage
temperature

50 °C (122 °F)

Maximum humidity,
operating or storage

95%, non-condensing.

Enclosure options

General Purpose 3R enclosure

Insertion impedance

Approximately 6.5% at 60 Hz & full load current

Capacitors

Oil filled high endurance design (no PCBs)

Table 10b – Only with Board Option

Status indication LEDs

Green LED indicates: "Control Power ON"
Yellow LED indicates: "Normal Operation" (not faulted)

Fault relay

De-energized when a fault is detected.
Form C contact for customer use.
Rated 0.6 A at 125 VAC and 110 VDC, 2 A at 30 VDC.