Table 11 – Motor Power Terminal Wire Size Capacity Range and Tightening Torque (Cu or
Al) - Industrial

KMG IND

Model Numbers

Ground Lug

Input and Output

Motor Power

Wire Size

Torque
(in.-lb.)

Wire Size

Torque
(in.-lb.)

KMG8A to KMG55A

KMG8C to KMG45C

14 - 1/0 AWG

200

22 - 16 AWG

14 - 6 AWG

4 - 2 AWG and

1 AWG (7 & 19 strand only)

25
30
35

KMG65A to KMG130A

KMG55C to KMG130C

6 - 2/0 AWG

120

6 - 2/0 AWG

120

KMG160A to KMG200A

KMG160C to KMG200C

6 AWG - 250 MCM

275

6 AWG - 250 MCM

275

KMG250A to KMG305A

KMG250C to KMG305C

4 AWG - 600 MCM or

(2) 1/0 AWG - 250 MCM

500

4 AWG - 600 MCM or

(2) 1/0 AWG - 250 MCM

500

KMG362A

KMG362C to KMG420C

(2) 4 AWG - 350 MCM

275

(2) 4 AWG - 350 MCM

275

KMG420A to KMG600A

KMG500C to KMG600C

(2) 2 AWG - 600 MCM

500

(2) 2 AWG - 600 MCM

500

KMG750A

(3) 2 AWG - 600 MCM

375

(3) 2 AWG - 600 MCM

375

Table 11b – Motor Power Terminal Wire Size Capacity Range and Tightening Torque (Cu or
Al) – General Purpose

KMG GP

Model Numbers

Ground Lug

Input and Output

Motor Power

Wire Size

Torque
(in.-lb.)

Wire Size

Torque
(in.-lb.)

KMG55A
KMG45C

14 - 1/0 AWG

200

22 - 16 AWG

14 - 6 AWG

4 - 2 AWG and

1 AWG (7 & 19 strand only)

25
30
35

KMG65A to KMG130A

KMG55C to KMG130C

6 - 2/0 AWG

120

6 - 2/0 AWG

120

KMG160A to KMG200A

KMG160C to KMG200C

6 AWG - 250 MCM

275

6 AWG - 250 MCM

275

KMG250A to KMG305A

KMG250C to KMG305C

4 AWG - 600 MCM or

(2) 1/0 AWG - 250 MCM

500

4 AWG - 600 MCM or

(2) 1/0 AWG - 250 MCM

500

KMG362A

KMG362C to KMG420C

(2) 4 AWG - 350 MCM

275

(2) 4 AWG - 350 MCM

275

KMG420A to KMG600A

KMG500C to KMG600C

(2) 2 AWG - 600 MCM

500

(2) 2 AWG - 600 MCM

500

Connection Diagram

Figure 4 shows the typical wiring connections between the MotorGuard and the VFD and motor. Note
that separate conduits may be required for the control power and fault contact wiring. Refer to the