Troubleshooting – WarmlyYours TempZone Floor Heating Cable (Twin) User Manual

Page 28

Advertising
background image

Additional Information for Identifying Electrical Shorts

In some rare occasions during installation, a high pressure point on the cable can occur and cause a break in the insulation

between the core conductor and the metal sheath. This opening in the insulation layer can create an electrical short,

even though the ohm reading from one line conductor to the other line conductor is normal and does not indicate a

circuit break. In these rare circumstances, a continuity test will show no continuity (a reading of infinity) between the line

conductor and the ground wire and/or between the other line core conductor and the ground. A megaohm meter can be

used to test the wire insulation in these cases.

There should be no continuity (indicated by a resistance reading of infinity, not zero) between each line conductor and

ground. If the ohmmeter or PowerMan™ reveals continuity between both the line conductor and ground, there is a short in

the circuit.

8.2.4. Checking for Breaks or Shorts Using an Underground Fault Detector

There are two ways to locate breaks or electrical shorts with underground fault detectors:

1. A break or short can most easily be found with a high potential (hipot) insulation tester, a high-voltage generating device

that generates a ground or heat at the break point. The hipot can be used with infrared cameras to scan the floor and

detect the exact location of the break. Contact WarmlyYours for more information about renting our troubleshooting kit.

2. A break or short can sometimes be found with a time domain reflectometer (ShortStop fault finder), which measures the

distance of the wire between the tester and the short point. A floor plan with the layout of the installation is required to

determine the location of the short.

Troubleshooting

SECTION 8

25

Advertising