GuardShield™ Safe 4 Safety Light Curtain User Manual

11

Original instructions

Figure 11: Different mounting brackets for Safe 4

Safe 4 Shock Mounting Kit

Rockwell Automation offers a shock and vibration isolation kit for
vertically mounting the Safe 4. This kit is most effective in
protecting the internal optical and electronic components of the
Safe 4 light curtain. The best performance of the shock and
vibration isolation kit is attained when the kit is used in
conjunction with the Safe 4 vertical mounting brackets (445L-
AF6144).

Figure 12: Shock Isolator

Electrical Installation

Connections

Power Supply

The external voltage supply (+24V DC) must meet the
requirements of IEC 61496-1. In addition, the following
requirements have to be fulfilled:

• A short-term power failure of 20 ms must be bridged by the

power supply.

• The power supply has double insulation between the

primary and the secondary side.

• The power supply is protected against overload.

• The power supply corresponds to the guidelines of the EWG

(industrial environment).

• The power supply corresponds to the Low Voltage

Directives.

• The grounded conductor of the power supply device must

be connected to a grounded conductor PE.

• The maximum deviation of the voltage levels is 24V DC +/-

20%.

445L-AF6140
Standard mounting brackets—supplied with each
light curtain
For side mounting
Adjustable by

± 4°

(Two brackets per kit.)

445L-AF6144
Vertical mounting brackets (optional)
For mounting in the vertical axis of the light curtain
Adjustable by

± 4°

(Two brackets per kit.)

445L-AF6141
180° Mounting, rotation ±90°, for applications
where the mounting angle is not set using the
mounting frame.
(Two brackets per kit.)

29.5

(1.16)

M6x40

M4x16

11

(0.43)

M6x60

M4x12

11

17

(0.67)

135

(5.31)

40.8

(1.60)

70

(2.76)

36.4

(1.43)

37

(1.46)

M6

20

(0.79) dia.

M 6x25 Socket head cap screw, fully threaded

M 6x6.1/14 Lock washer

M 6x6.1/14 Lock washer

Vibration damper

18

(0.71)

20

(0.79)

Double insulation

This part of the insulation provides

supplementary insulation against

hazardous voltage levels.

Motor, etc.

Hazardous voltage level

Basic insulation

Hazardous

voltage level

Hazardous

voltage level

Reinforced

insulation or

double

insulation

Unit 1

Power

Supply

Unit 2

Output (pink

and grey)

Basic insulation

Basic insulation

0V (blue)

+24V (brown)

K1

K1

K2

K2

Guard
Shield