Torque specifications, Scr module access, Scr module access” on – Rockwell Automation 1336S, 1336F, 1336E, 1336T, 1336-SN-SP18A Snubber Board Kit User Manual

Page 11

Advertising
background image

1336-5.39 – August, 1999

I-11

Torque Specifications

The following table lists fastener locations by component,
application, and torque specifications. Refer to “Torque Sequence” on
page I-4
for fastening two-point, four-point, and six-point
components to the heat sink.

SCR Module Access

Important: Before you remove connections and wires from the drive
components, mark the connections and wires to correspond with their
component connections and terminals to prevent incorrect wiring
during assembly.

Component

Fastener Application

Fastener Used

Torque

in.-lb

Torque

N-m

SCR Module

Module to Heat Sink

M6 x 16 mm Screw

52

5.9

Snubber Board

Board to SCR

M4 x 8 mm Screw

12 – 16

1.4 – 1.8

Gate Driver Board Mounting Plate

Plate to Chassis

M5 x 10 mm Screw

23 – 36

2.6 – 4.1

Control Board Mounting Plate

Plate to Gate Driver Board Mounting Plate

M6 Nut

23 – 36

2.6 – 4.1

Control Board Mounting Plate

Plate to Gate Driver Board Mounting Plate

M4 x 8 mm Screw

12 – 16

1.4 – 1.8

Enclosure Bottom, Top, and Side Panels

Enclosure Sheet Metal

M5 x 10 mm Screw

23 – 36

2.6 – 4.1

TB1 Wires

Wires to TB1

M8 Nut

52

5.9

Converter Bus Bar Wires

Wires to Converter Bus Bar

M6 x 12 mm Screw

50 – 72

5.6 – 8.1

Ground Wire TE (Gate Driver Board)

Wire to TB1 Terminal TE

Compression

6 – 8

0.7 – 0.9

TB20 Wires, PLC Comm Adapter Board

Wires to TB20

Captive Screw

TB21 Wires, PLC Comm Adapter Board

Wires to TB21 on Main Control Board

Captive Screw

TB5 Wires, Standard Adapter Board

Wires to TB5 on Main Control Board

Captive Screw

12 – 16

1.4 – 1.8

TB6 Wires, Standard Adapter Board

Wires to TB6 on Main Control Board

Captive Screw

12 – 16

1.4 – 1.8

TB7 Wires, Standard Adapter Board

Wires to TB7 on Main Control Board

Captive Screw

12 – 16

1.4 – 1.8

TB3 Wires, Standard Adapter or
L-Option Board

Wires to TB3 on Control Interface Board or
L-Option Board

Captive Screw

8 – 10

0.9 – 1.1

Enclosure Door Ground Wire

Wire to Enclosure Door

M6 Nut

23 – 36

2.6 – 4.1

!

ATTENTION: Disconnect and lock out power from
the drive before disassembling the drive. Failure to
disconnect power may result in death or serious injury.
Verify bus voltage by measuring the voltage between
+DC and -DC on Terminal Block TB1. Do not attempt
to service the drive until the bus voltage has discharged
to zero volts.

ATTENTION: Wear a wrist-type grounding strap
when servicing drives. Failure to protect drive
components against ESD may damage drive
components. Refer to “Electrostatic Discharge
Precautions” on page I-4
.

Advertising