Remove power from the drive, Open the enclosure door, Check for zero volts at tb1 terminals +dc and -dc – Rockwell Automation 1336S, 1336F, 1336E, 1336T, 1336-SN-SP18A Snubber Board Kit User Manual

Page 17: Check for the absence of control voltage at

Advertising
background image

1336-5.39 – August, 1999

I-17

1. Remove power from the drive.

2. Open the Enclosure door.

3. Check for zero volts at TB1 terminals +DC and -DC.

4. Check for the absence of control voltage at:

TB2

TB3

5. Disconnect the following from the Main Control Board:

J2 ribbon cable connector

J1 connector

Ground wire at terminal block TE

J10 ground wire at the stake-on connector

J6 connector

J8 connector

All wires from the terminals on TB2 and TB3

6. Remove the nuts at the top of the Main Control Board Mounting

Plate.

7. Remove the two screws at the bottom of the Main Control Board

Mounting Plate.

8. Lift the Main Control Board Mounting Plate out of the drive.

9. Continue with “Gate Driver Board and Precharge Board

Mounting Plates” on page I-20.

Drive shown with door open, sides removed.

Advertising