Rockwell Automation Publication 1608N-UM002B-EN-P - May 2014

11

Installation

Chapter 1

Line to Line

MiniDySC L-L models must be connected as in

Figure 7

to operate properly.

Figure 7 - Line to Line Configuration

Completing Terminations

Output terminals are marked X1 and N or X1 and X2. If multiple loads are
served by the MiniDySC a separate distribution box must be provided. Only one
conductor should be terminated in each MiniDySC terminal block position.
Terminal torque requirements are shown in

Figure 8

,

Figure 9

,

Figure 10

, and

Figure 11

.

Figure 8 - 12 and 25 Amp Standard Ride-through (SR)

25A ER

50A SR/ER

GR

X2

X1

L2

L1

GR

L1

L2

X2

X1

GR

X2

X1

L2

L1

12A-25A SR

INPUT SOURCE

User Supplied

Circuit Breaker

L1

L2

GND

GROUND

STUD

OUTPUT TO LOADS

X1

X2

GND

X1

X2

L2

L1

L-L

Terminal Block Configurations

TERMINAL BLOCK

INPUT/OUTPUT TERMINAL RATING:

22-8 AWG (0.5-6mm2)

TORQUE: 7.1-8.9 lb-in.

(0.8-1.0 N-m)

WIRE STRIP LENGTH: .47" [12mm]

LINE TO LINE

LINE TO NEUTRAL

#10-32 GROUND STUD

TORQUE: 29 in-lb.

(3.3 N-m)

OR

FUSE

L1-N-N-X1-GR

L1-L2-X1-X2-GR