Figure 9 - 25 amp extended ride through (er), Figure 9, Figure 10 – Rockwell Automation 1608N MiniDySC User Manual, 12-50 Amp User Manual

Page 12

Advertising
background image

12

Rockwell Automation Publication 1608N-UM002B-EN-P - May 2014

Chapter 1

Installation

Figure 9 - 25 Amp Extended Ride Through (ER)

Figure 10 - 50 Amp Standard/Extended Ride-through (SR/ER)

INPUT/OUTPUT TERMINAL RATING:

22-8 AWG (0.5-6mm2)

TORQUE: 7.1-8.9 lb-in.

(0.8-1.0 N-m)

WIRE STRIP LENGTH: .47" [12mm]

FUSE

1/4-20 GROUND STUD

TORQUE: 65 in-lb.

(7.3 N-m)

LINE TO NEUTRAL

LINE TO LINE

TERMINAL BLOCK

OR

L1-L2-X1-X2-GR

L1-N-N-X1-GR

OR

LINE TO NEUTRAL

LINE TO LINE

FUSE

TERMINAL BLOCK

1/4-20 GROUND STUD

TORQUE: 65 in-lb.

(7.3 N-m)

INPUT/OUTPUT TERMINAL RATING:

16-0 AWG (1.5 - 50 mm2)

TORQUE: 24.3-26.1 lb-in.

(2.7 - 2.9 N-m)

WIRE STRIP LENGTH: .67" [17mm]

GR TERMINAL RATING:

22-8AWG (0.5-6mm2)

TORQUE: 7.1-8.9 lb.-in.

(0.8-1 N-m)

WIRE STRIP LENGTH: .47" [12mm]

X1-N-N-L1-GR

X1-X2-L2-L1-GR