Figure 9 - 25 amp extended ride through (er), Figure 9, Figure 10 – Rockwell Automation 1608N MiniDySC User Manual, 12-50 Amp User Manual
Page 12
12
Rockwell Automation Publication 1608N-UM002B-EN-P - May 2014
Chapter 1
Installation
Figure 9 - 25 Amp Extended Ride Through (ER)
Figure 10 - 50 Amp Standard/Extended Ride-through (SR/ER)
INPUT/OUTPUT TERMINAL RATING:
22-8 AWG (0.5-6mm2)
TORQUE: 7.1-8.9 lb-in.
(0.8-1.0 N-m)
WIRE STRIP LENGTH: .47" [12mm]
FUSE
1/4-20 GROUND STUD
TORQUE: 65 in-lb.
(7.3 N-m)
LINE TO NEUTRAL
LINE TO LINE
TERMINAL BLOCK
OR
L1-L2-X1-X2-GR
L1-N-N-X1-GR
OR
LINE TO NEUTRAL
LINE TO LINE
FUSE
TERMINAL BLOCK
1/4-20 GROUND STUD
TORQUE: 65 in-lb.
(7.3 N-m)
INPUT/OUTPUT TERMINAL RATING:
16-0 AWG (1.5 - 50 mm2)
TORQUE: 24.3-26.1 lb-in.
(2.7 - 2.9 N-m)
WIRE STRIP LENGTH: .67" [17mm]
GR TERMINAL RATING:
22-8AWG (0.5-6mm2)
TORQUE: 7.1-8.9 lb.-in.
(0.8-1 N-m)
WIRE STRIP LENGTH: .47" [12mm]
X1-N-N-L1-GR
X1-X2-L2-L1-GR