Specifications and Dimensions

Table 5 - Technical Specifications – MiniDySC (12…50 Amps)

Electrical Input/Output (Normal Mode—Static Switch)

Connection Configuration

Series-connected with load. Under normal line condition, the static switch passes utility voltage directly to the load

Standard Input Voltage DySC

1Phase: 120, 208, 220, 230, 240V

Voltage Range

± 10%

Output Current (Static Switch)

0...100% of rated rms current, continuous

Current Overload (Static Switch) for 12A, 50A models 200% @ 30 Sec., 400% @ 5 Sec., 600% @ 0.5 Sec.

Current Overload (Static Switch) for 25A models

200% @ 30 Sec., 280% @ 5 Sec., 450% @ 0.5 Sec.

Frequency

50/60 Hz Auto Sensing

Frequency Range (tracking)

45 to 65 Hz

Surge Protection Device (SPD)

Built-in 3-Layers consisting of MOVs & Capacitors

Efficiency

> 98%

Phase (wiring)

1 phase (L-L & L-N)

Sag Detection Voltage

88.5% of rated voltage

Response Time (typical)

0.7 ms detection, 1.2 ms inverter reaction (<2ms)

Electrical Output (Sag Correction Mode—Inverter)

Output Voltage

Matches pre-sag input voltage

Voltage Regulation

+/- 5% typical, +5% / -13% of nominal max

Output Current

Rated RMS (12, 25, or 50 A)

Crest Factor (at rated load)

1.45

Load

Power factor range -0.5 to +0.9
DC component <2% of rated current

Voltage Waveform (typical)

Sine wave

Voltage Sag Correction Times

Single Event

87% to 50% voltage remaining

5 seconds SR & ER

Sags to zero voltage remaining

50ms or 200ms (SR or ER). Based on load at nameplate ratings with a power factor of 0.7

Multiple Events

Max Sag Correction Time

5 seconds cumulative usage

Seqential Sag Recovery

0 seconds (assuming cumulative run-time available)

Full Recovery Time

Max 5 minutes to full recovery

Mechanical

Enclosure Ratings

NEMA 1 (IP20)

Cable Entry

Bottom

Cooling

Forced Air

Access

Lower front for servicing and connections

Accessibility (Wiring)

DIN compression terminal block

Communications / User Interface

Indicators

Normal and Alarm LEDs

Connectivity

OUTPUT OK and ALARM contacts, Form A, 24VDC at 1A

Environmental

Ambient Temperature

0 ...+40°C

Storage Temperature

-40°C ...+75°C

Relative Humidity

0 to 95% non-condensing

Altitude

Rated current available to 1000m (3300ft). De-rate output current 10% per 1000m, from 1000m to 3000m (9900ft).

Heat Dissipation (max)

12A – 100 BTU/Hr 25A – 160 BTU/Hr 50A – 320 BTU/Hr.

Audible Noise

< 50dBA at 1 meter

Certifications

Agency Approvals

cULus 1012 Listed, Exceeds SEMI F47 Standard