Circuit breaker recommendations, Table 3 - circuit breaker recommendations, Electrical terminations – Rockwell Automation 1608N MiniDySC User Manual, 12-50 Amp User Manual
Page 9: Figure 4 - power terminal locations
Advertising
Rockwell Automation Publication 1608N-UM002B-EN-P - May 2014
9
Installation
Chapter 1
Circuit Breaker Recommendations
Branch circuit protection upstream of the MiniDySC is required
Table 3 - Circuit Breaker Recommendations
Electrical Terminations
A qualified electrician must install the MiniDySC. To access the connections,
remove the four screws on the bottom cover and lift off the cover. The MiniDySC
is furnished with one of the terminal block configurations as shown in the figures
below.
Figure 4 - Power Terminal Locations
Rated MiniDySC (Amps)
Maximum Rated Breaker (Amps)
12
15
25
35
50
70